Description:
The AVC125-10 Voltage Regulators are contained in an encapsulated plastic case. The regulator controls the DC exciter fi eld power of conventional, 50 or 60 Hz brushless genera tors.Regulation is provided by sensing the generator output voltage, converting it to a DC signal and comparing the signal to a reference voltage signal. An error signal is developed and used to control the DC fi eld power in order to maintain a constant generator output. The regulator includes frequency compensation with selectable slope,inverse time over-excitation shutdown, solid-state build-up circuitry,single-phase or three-phase voltage sensing, single-phase or threephase shunt, or permanent magnet power input, and parallel droop compensation, and an accessory input. The accessory input provides compatibility with accessories such as a var/power factor controller.
Basler AVR AVC125-10
Power: SHUNT EXCITED
Input: 180-280 Vac, 50/60 Hz, 1 OR 3 phase
PMG EXCITED 63-105 Vac 100/240 Hz 3 phase
Sensing input: 90-140 Vac, 50/60 Hz 1 OR 3 phase
CT input: 1 or 5 Aac 50/60 Hz
ACC input: +/- 3 Vdc. Output: 125 Vdc @ 10 Adc
Unit Type: piece
Package weight: 1.5kg
Package size: 24.0*18.0*9.0cm(9.4*7.1*3.5in)
Technical data:
Specification |
Balser AVR AVC125-10 |
Output power (with a 240 Vac Input): |
10 Adc @ 125 Vdc maximum |
AC input power: |
100 to 280 Vac, single-phase 50 |
AC sensing voltage: |
90 to 140Vac, 50/60 Hz; single- or |
External voltage adjust |
10k ohm, 2 W, potentiometer |
Regulation accuracy: |
±0.5% Average responding |
Voltage drift: |
±1% voltage variation for a 40° C |
Response time: |
lt; 4 milliseconds |
Frequency compensation: |
1 or 2 V/Hz jumper selectable with |
EMI suppression: |
Internal filter |
Voltage Build-Up: |
Internal provisions for automatic |
Over excitation shutdown: |
Over excitation protection starts |
Droop |
1 Aor 5 A, lt;10 VA, adjustable from |
UL recognized/CSA |
UL Recognized per Standard 508, |